The FC-RUSIO-3224 module has 32 remote universal safe IO channels. One FC-RUSIO-3224 module can be placed on a non-redundant IOTA to establish 32 non-redundant channels. Two FC-RUSIO-3224 modules can be placed on one redundant IOTA to establish 32 redundant universal safe IO channels.
Marque :
HoneywellNuméro d'article :
FC-RUSIO-3224Description :
Universal Safe I/O ModuleOrigine :
SlovakiaCondition :
NewDimension :
145 mm x 165.1 mm x 72.4 mmPoids :
0.66 kgPaiement :
Bank Transfer
Honeywell FC-RUSIO-3224 Universal Safe I/O Module
Functional Description
The FC-RUSIO-3224 module has 32 universal safe IO channels with configurable channel function;
configuration is done in Safety Builder.
The FC-RUSIO-3224 module can be used in applications up to SIL 3, in compliance with IEC 61508/61511.
It requires two RUSIO-3224 modules to achieve a redundant configuration. All channels are powered out of
the 24 V DC supply.
Each channel can be configured as:
· Digital input (with or without loop monitoring)
· Digital output (with loop monitoring
· Analog input (0-20 mA or 4-20 mA active)
· Analog output (0-20 mA or 4-20 mA active)
The FC-RUSIO-3224 module supports two (100Mbaud) ethernet links to communicate with a Safety Manager
Controller.
The FC-RUSIO-3224 module has a housing that is in line with the patented Series C design of Honeywell. It
needs to be placed on an IO Termination Assembly (IOTA).
The FC-RUSIO-3224 module has the following features:
· 32 universal IO channels that can be configured to control DI, AI, DO, AO
· Any type of IO field signal has only to be connected to the two connections of the applicable universal
channel on the IOTA
· Proven-in-use redundant processor concept that complies with the SIL 3 safety requirements in single
channel operation
· A dedicated communication link between these processors
· A redundant communication link with the partner module (in redundant configuration)
· An Ethernet-based Safety Manager Universal I/O link to the Safety Manager Controller in the network via
dedicated switches; the Safety Manager Universal I/O link uses a dedicated protocol
· Monitoring the temperature of the electronics
· A configurable ESD function via channel 32 for dedicated safety related functions
· Function-tested watchdogs that: monitor and/or handle:
· monitor cycle time and supply voltage
· handle the ESD function and memory errors
· LED indicators at the front of the module for power and health status indication
· Real-time clock for Sequence Of Event (SOE) time stamping with a resolution of 1 msec
The FC-RUSIO-3224 module functions as a Safety Manager universal IO module within the Safety Manager
concept. It executes:
· The input scan of the process variables
· All functional tests of its hardware
· Data exchange with its partner module
· Data exchange via the Safety Manager Universal I/O link with the Safety Manager Controller that
executes the application logics
· Update the outputs and thus the process
The FLASH nature of the memory allows for on line upgrading within the TÜV-approved concept of both
the system software as well as the channel configuration.
Technical Specifications
General | Type number: | FC-RUSIO-3224 |
Operating temperature: | ||
· outside module temperature: | -40°C ... +70°C (-40°F ... +158°F) | |
· inside module temperature: | -40°C ... +90°C (-40°F ... +194°F) | |
Storage temperature: | -40°C ... +85°C (-40°F ... +185°F) | |
Relative humidity: | 10 ... 95% (non condensing) | |
Pollution: | Pollution degree 2 or better | |
Approvals: | CE, UL, TÜV | |
Power | Supply voltage: | 24 V DC -15% ... +30% |
Supply current: | max 300mA (without field load) | |
IO | Number of channels: | 32 |
Channel type: | Universal safe (software configurable) | |
· Digital in | max. 32 (with or without line-monitoring) | |
· ESD in | max. 1 (with line-monitoring) | |
· Analog in | max. 32 (with or without line-monitoring) | |
· Digital out | max. 32 (with or without line-monitoring) max. combined load: 9 A |
|
· Analog out | max. 16 (with or without open loop detection) |
|
Maximum field capacitance | 100 nF (for AI / DI / AO channels) | |
1 μF (for DO channels) | ||
Physical Data | Dimensions (H x W x D): | 145 x 165.1 x 72.4 mm |
5.7 x 6.5 x 2.85 in | ||
Weight: | 0.66 kg | |